Product Overview:

The size, durability and flexibility of the range makes it ideal for use in
all types of commercial and residential property including small shops,
factories, schools, warehouses, offices and houses in multiple occupation.
Often referred to as ‘the installer’s choice’, easy-to-follow wiring
instructions are printed adjacent to the terminals of all variants and a
lift-off lid guarantees an easy first fix and straightforward maintenance.
The panel’s broad compatibility with virtually all known smoke and heat
detector ranges and its ability to interpret a short circuit in any zone(s)
as a fire or fault condition make it particularly useful for retro-installations.

Standard Features:

C-TEC’s FP Range of conventional fire alarm control panels is one of the most robust andcost-effective available.Fully compliant with BS 5839 part 4, the range encompasses no less than ten different variants, covering 1 to 14 zones.

  • Fully compliant with BS 5839 Part 4
  • Lift-off lid for easy first fix and maintenanceAttractive easy-to-clean polycarbonate front labelHeavy-duty base connections

    Robust metal lid and metal back box

    Ultra-bright, long-life LED indicators

    Built-in 24V power supply and battery charger

    Optional head removal facility for compliance

    with BS 5839 Part 1

  • Short circuit = fire facility (pre-1980 BS, noresistors in call points), selectable on a zone byzone basis for retro-installations

    True battery monitoring circuit

    One man walk test and zone isolate facility

    (not available on EFP1)

    Ancillary connections for repeater panels and

    other system add- including fault relay

    modules, fire relay modules, sounder delay

    relay modules, sounder extender kits, etc

    (not available on EFP1)

Technical Specifications
Mains supply 230V 50/60Hz..
Internal power supply 27V nominal..
Total output current limited to 1400mA @ 230V.
Quiescent current 70mA
Max battery size and type 2 x 12V 3.2Ah VRLA connected in series
No. of detector zone circuits 8 (Max. length per circuit is 500m).
Call point resistor value 470 to 680Ω
Max. devices per detector zone 20 detectors
No. of conventional sounder circuits 2 (Max. length per circuit is 500m).
EOL resistor value 6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Max. sounder output current 1400mA (to all outputs). Outputs are fused at 1A.
Weight 5.0kg.