Mains supply |
230V 50/60Hz.. |
Internal power supply |
27V nominal.. |
Total output current limited to |
800mA @ 230V. |
Quiescent current |
50mA |
Max battery size and type |
2 x 12V 2.3Ah VRLA connected in series |
No. of detector zone circuits |
4 (Max. length per circuit is 500m). |
Call point resistor value |
470 to 680Ω |
Max. devices per detector zone |
20 detectors |
No. of conventional sounder circuits |
2 (Max. length per circuit is 500m). |
EOL resistor value |
6800Ω 5% Tol. 0/25W (blue, grey, red, gold). |
Max. sounder output current |
800mA (to all outputs). Outputs are fused at 1A. |
Weight |
4.3kg. |
|
|