• 0332-5284828, 051-4427778
  • info@universalfireprotection.com.pk
c-tek
  • FP 4 Zone Economy Conventional Fire Alarm Panel has a Installer-friendly design.
  • FP 4 Zone Economy Conventional Fire Alarm Panel  comes with Robust metal enclosure c/w lift off lid & heavy-duty base connections.
  • It Has 4 conventional Zone circuits.
  • It has also two conventional Sounder circuits
  • FP 4 Zone Economy Conventional Fire Alarm Panel  have a Separate indicators for both open & short circuit fault, sounder fault and battery/power supply fault.

Technical Specifications
Mains supply 230V 50/60Hz..
Internal power supply 27V nominal..
Total output current limited to 800mA @ 230V.
Quiescent current 50mA
Max battery size and type 2 x 12V 2.3Ah VRLA connected in series
No. of detector zone circuits 4 (Max. length per circuit is 500m).
Call point resistor value 470 to 680Ω
Max. devices per detector zone 20 detectors
No. of conventional sounder circuits 2 (Max. length per circuit is 500m).
EOL resistor value 6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Max. sounder output current 800mA (to all outputs). Outputs are fused at 1A.
Weight 4.3kg.
Rate this page